    Home > Products & Services > Ice Thermal Storage > District Cooling

    District Cooling

    2.Benefits

    Date : 2013-10-21 00:17
    QWhy Ice Thermal Storage for District Cooling Projects?
    ABecause only ice, on a simple and practical basis, can provide a constant 34°F (1°C) supply fluid temperature that yields:
    1. Lowest first cost system that does not require utility incentives
    2. Reduced energy costs by providing flexibility in when energy is used and reducing the total system kWh usage
    3. Reduced maintenance by using smaller equipment with flexibility in service schedules
    4. Improved system reliability ensuring constant cooling
    5. Space savings with reduced equipment room and heat rejection requirements
    6. Environmentally friendly systems with reduced energy consumption and global warming

    ?填充圖片

    Lowest First Cost

    image002image004
    An ice storage system that takes advantage of low temperature fluid is the lowest first cost design. Substantial savings in the chilled water distribution system are realized when the system design incorporates reduced flow rates that result from using a larger temperature range in the water loop. Use of a 20°F (11°C) temperature range instead of a conventional 10°F (5.6°C) to 14°F (7.8°C) temperature range results in a substantial reduction in pipe size. Smaller distribution piping can often be installed via trenching versures tunneling, allowing the piping to be installed with less time and expense.
    The savings that result from the use of smaller distribution piping offset the cost of the thermal storage equipment. A 16,000 ton (5,632 Mw) district cooling plant designed with centrifugal chillers using 44°F (7°C) supply water and one with ice storage using 34°F (1°C) supply water were compared. The conventional plant required 30in (762 mm) diameter distribution piping ($7,680,000 installed) versus 18in (457 mm) for the ice storage system ($5,340,000 installed) that yielded savings of $2,340,000.

    Cost

    44°F (7°C) Supply Water System

    34°F (1°C) Supply Water System

    Chiller Equipment

    2,960,000

    2,865,000

    Cooling Towers $ Evaporative Condensers

    623,725

    588,838

    Pumping Equipment

    551,905

    402,106

    Thermal Storage Equipment

    N/A

    2,957,920

    Equipment Rigging

    206,781

    289,666

    Mechanical Piping

    2,560,000

    2,711,200

    Mechanical Insulation

    844,800

    894,696

    Refrigerant

    224,800

    73,132

    Refrigerant

    224,800

    73,132

    Plant Ventilation

    16,733

    99,934

    Automation System

    993,218

    1,805,987

    Electrical Equipment

    2,475,742

    1,835,634

    Building Cost

    3,960,000

    2,645,775

    Sales Tax (Equipment & Material)

    600,138

    624,536

    CONSTRUCTION COSTS

    16,017,042

    624,536

    Project Management $ Engineering

    1,927,113

    2,053,249

    Project Contingency

    897,208

    995,401

    TOTAL PLANT COST

    16,017,042

    624,536

    Street Distribution Piping Cost Estimate

    6,000 Linear Feet: Trenching & Restoration

    5,820,000

    3,960,000

    12,000 Linear Feet of Supply and Return Piping

    1,860,000

    1,380,000

    TOTAL STREET PIPING COST

    7,680,000

    5,340,000

    Total Building Connections Cost Estimate

    Heat Exchangers

    960,000

    422,400

    Stations

    560,000

    480,00

    Piping, Erection & Insulation

    2,960,000

    1,977,600

    TOTAL BUILDING CONNECTION COST

    4,480,000

    2,880,000

    16,000 TON COOLING SYSTEM TOTAL

    31,001,363

    28,303,324

    ?填充圖片

    Reduced Energy Cost

    With smaller mechanical equipment, ice thermal storage can lower electrical demand charges up to 50%. In addition, total annual energy consumption is less because of the lower pumping horsepower (kW). As the electric industry continues to deregulate, and time-of-use rates, real time pricing schedules and negotiated power prices become standard, ice storage can provide even greater future savings in operating costs.
    In a comparison of a 16,000 ton (5,632 MW) district cooling plant designed with centrifugal chillers using 44°F (6.7°C) supply water and one with ice storage using 34°F (1°C) supply water, the peak demand was 15,985 kW for the conventional plant and 10,135 kW for the ice plant, a 37% reduction in peak demand.
    image005

    ?填充圖片

    Reduced Maintenance

    The ice storage coils have no moving parts so very little maintenance is required. The only ice thermal storage maintenance required includes the air pump, system fluid and controls. Because the chillers, pumps and heat rejection equipment are smaller, the ice storage system will have less maintenance than a conventional system.
    image010image008

    ?填充圖片

    Improved System Reliability

    image012 Ice Storage systems provide the reliability necessary to ensure air-conditioning is available. With conventional systems, installing multiple chillers provides redundancy. In the event of a mechanical failure of one chiller, the second chiller provides limited cooling capacity. The maximum available cooling for the conventional system would only be 50% on a design day.
    Most ice storage systems utilize two chillers in addition to the ice storage equipment. Two chillers are designed to provide approximately 60% of the required cooling on a design day while the ice storage provides the remaining 40% of the cooling capacity. In the event only one chiller is available to provide cooling during the day, up to 70% of the cooling capacity is available. The one operable chiller provides 30% of the cooling requirement while the ice provides up to 40%. Base on typical HVAC load profiles and ASHRAE weather data, 70% of the cooling capacity would meet the total daily cooling requirements 85% of the time.

    ?填充圖片

    Space Savings

    Ice Thermal Storage saves equipment room and heat rejection space since smaller chillers, pumps and heat rejection equipment is required. A district cooling plant with ice thermal storage requires two-thirds of the chiller and heat rejection capacity of a conventional system. The chilled water pumps will be half the size of a typical 10°F (5.6°C) temperature differential system, and the condenser water pumps will be two-thirds the size of a conventional system. The plan area required for the equipment room and heat rejection equipment can be cut by one-third. The thermal storage can be located outdoors, in a sub-basement or under a parking lot, it does not have to be part of the equipment room.

    Chilled water storage requires 4 to 10 times the space of ice thermal storage. The use of sensible cooling combined with storage inefficiencies make chilled water storage tanks larger.

    image014

    傳統系統的設備室

    image016

    填充圖片

    Environmentally Friendly

    image017 Reducing energy consumption and using electricity at night will reduce global warming. District cooling, using new energy efficient water-cooled chillers and ice storage, will significantly reduce energy consumption. Electricity generated at night generally has a lower heat rate (lower fuel use per power output), and therefore, lower carbon dioxide and greenhouse gas emissions resulting in less global warming.The California Energy Commission concluded that the use of electricity at night created a 31% reduction in air emissions over the use of electricity during the day. The use of an environmentally friendly and energy efficiency ammonia refrigerant, can be considered for may district cooling systems.
    ?
    主站蜘蛛池模板: 日本韩无专砖码高清| 亚洲精品在线二区三区| 亚洲欧美自拍偷拍| 99精品视频免费热播在线观看| 国产亚洲中文| 桐柏县| 亚洲最大国产成人综合网站| 日本亚洲欧洲无免费码在线| 精品国产91久久久久久亚瑟| 综合久久少妇中文字幕| 亚洲av影院一区二区三区| 国产熟人av一二三区| 97r久久精品国产99国产精 | 美女胸18下看禁止免费视频| 18禁黄污无遮挡无码网站| 久草热在线视频免费播放| 两个人看的www视频免费完整版| 亚洲伊人久久大香线蕉AV| 久久99国产亚洲高清观看首页| 久久综合之色之久久| 蜜臀98精品国产免费观看| 人妻无码中出| 国产乱码精品一区三上| 国产女人爽的流水毛片| 和黑人中出一区二区三区| eeuss国产一区二区三区| 亚洲av天天| 欧美激情,国产精品| 亚洲日本乱码中文在线电影亚洲 | 人妻人久久精品中文字幕| 欧美黑吊大战白妞| A片在线不卡观看免费观看| 亚洲综合精品一区二区三区 | 中文字幕人妻互换av久久| 亚洲人妻视频| 亚洲AⅤ色无码乱码精品| 男人天堂2025| 成人国产精品视频频| 国产 另类 在线 欧美日韩| 日本一区二区不卡精品| 亚洲理论片|